eWON wiki > eWON Support > Knowledge Base > Questions and Answers > IOServer Status Tag not refreshed
IOServer Status Tag not refreshedFrom $1Table of contentsWhen I defined a Status Tag in a IOServer, it stays to 0, even if the target device is well connected?It happens when you define only the Status Tag without any other tags. Solution: create another Tag on the same target The Status Tag is not a true IOServer register, it's an eWON internal register that reflects the state of the communications. |