eWON wiki > eWON Support > Knowledge Base > Questions and Answers > WinCC flexible® Runtime and eVCOM

WinCC flexible® Runtime and eVCOM

From $1

Table of contents

 

Using WinCC flexible@ Runtime through an eWON eVCOM connection, you may encounter connection interruptions when a page with many tags is displayed.

To solve the problem, in WinCC disable the "Cyclic operation" in the Connection Settings. See picture hereunder. 

 WinCC_CyclicOperation.png

The "Cyclic operation" option allows data exchange optimization between the PLC and the HMI device but is not supported by the eWON eVCOM solution.